Coffee Break Bulletin

Hydraulic system nameplates

Posted: July 31, 2017

This Coffee Break Bulletin explains what information is required by National Fire Protection Association (NFPA) Standard 13, "Standard for the Installation of Automatic Sprinkler Systems (2016 Edition)," on a fire sprinkler system’s hydraulic nameplate.

fire sprinkler system

Most automatic sprinkler systems designed today are hydraulically calculated — an engineered approach that matches the potential fire hazard to the pressure and volume of the available water supply. The sprinkler plans examiner verifies the hydraulic calculations to ensure that all of the design considerations are met.

To help keep track of the design criteria, NFPA 13 requires that the installing contractor identify hydraulically designed sprinkler systems with a permanently marked weatherproof metal or rigid plastic sign secured with corrosion-resistant wire, chain, or other approved means. The sign must be placed at the alarm valve, dry-pipe valve, preaction valve, or deluge valve supplying the corresponding hydraulically designed area.

According to NFPA 13, the sign must have the following minimum information:

  • The location of the design area(s). These are also known as the “hydraulic remote areas” and make up the portion of the building and contents that are most challenging for the sprinkler system to protect. It is important to remember that the hydraulic remote area may not be the area physically most remote from the sprinkler risers.
  • The discharge densities over the design area or areas. This is the amount of water that the design criteria specify is needed to control a fire in the hydraulic remote area. This value may come from NFPA 13 or the authority having jurisdiction.
  • The required flow and residual pressure demand at the base of the riser.
  • Occupancy classification or commodity classification and maximum permitted storage height and configuration.
  • Hose stream allowance included in addition to the sprinkler demand.
  • The name of the installing contractor.
photo of a hydraulic name plate with information filled in

Action step for learning more about the installation of fire sprinkler systems

Review NFPA 13 to stay up-to-code with the industry standard for installation of automatic sprinkler systems.

Explore more Coffee Break Bulletins:

Subscribe to our email list

Keep up with Coffee Break Bulletins by having them delivered straight to your inbox. Subscribe